Korea YTC Electro Pneumatic Positioner YT-1000L YT-1000L+SPTM
The Electro-Pneumatic Positioner YT-1000L is used for operating of pneuamtic rotary valve actuators by means of electrical controller or control system with an analog output signal of DC4-20 mA or split ranges.
Specifications:
Enclosure | IP66 | ||
Ambient Temp. | Operating | -20~70 ℃ | |
Explosion | -20~60 ℃ | ||
Linearity | ±1% F.S. | ±2% F.S. | |
Hysteresis | ±1% F.S. | ||
Sensitivity | ±0.2% F.S. | ±0.5% F.S. | |
Repeatability | ±0.5% F.S. | ||
Air Consumption | 2.5LPM (sup=0.14 MPa) | ||
Flow Capacity | 80LPM (sup=0.14 MPa) | ||
Material | Aluminium Diecasting | ||
Weight | 2.8 kg |
:
Drawings:
YT-1000L
Pictures details:
Delivery
1. If the products we have in store, we will send it out ASAP after payment.
2. If the products which were customized, we will complete the production within a specified period of time, and send it out the first time, we can promise it.
3. Also we can send by your delivery acount if you want.
4. We have a variety of ways to send goods, usually DHL, Fedex, TNL will be normal ways. If you require use of a courier, we can do it.
Competitive Advantage
Our product features | Our Services Guarantee: |
1) Competitive price | 1) Prompt respond (Reply with 24 hours) |
2) Good quality | 2) Free Samples (Customer pay for the delivery cost) |
3) Professional Packaging | 3) Registration support. |
4) Produce according to Customers’ instruction | 4) Photos/videos are available during production. |
5) None delay shipment | 5) Loading inspection, and send loading photos before shipment. |
After-sale Service
We can provide a series of after-sale service, such as product introduction, mounting, debugging, technical support and so on.
Warranty
All item Comes with Basic 3 Month Sellers Warranty, if item defective in 3 Month, We will offer replacement without extra Charger(including shipping fee)After we Receive the Defective item.
If item Defective after 3 Month, Buyers can still send it back, We will contact suppliers or Manufactory for Warranty. Buyers Might Need to pay the Shipping fee For resend the replaced item.
Installation
Safety Warning
When installing positioner, please ensure to read and follow safety instruction.
All input and supply pressure to valve, actuator, and other related devices must be turned
off.
Use bypass valve or other equipment to avoid entire system "shut down."
Make sure there is no remaining pressure in the actuator.
Tools for installation
① Hexagonal wrench
② Screw drivers (+) & (-)
③ Spanners for hexagonal-head bolts
YT-1000L installation
YT-1000L should be installed on linear motion valve such as globe valve or gate valve using spring
return type diaphragm or piston actuator. Before installation, be sure to check for following
installation components.
① YT-1000L main body
② Feedback lever and lever spring
③ Flange nut (bottom side of YT-1000L)
④ 4 pcs. of hexagon head bolts (M8 X 1.25P)
⑤ 4 pcs. of M8 plate washer