Add to Cart
describe | |
SITOP BATTERY MODULE/24V/7AH SITOP battery module 24 V/7 Ah with maintenance free sealed lead batteries for SITOP DC UPS module 6 A, 15 A and 40 A *Ex approval no longer available* | |
Charging current charging voltage | |
end-of-charge voltage at DC | |
● at -10 °C recommended | 29 V |
● at 0 °C recommended | 28.4 V |
● at 10 °C recommended | 27.8 V |
● at 20 °C recommended | 27.3 V |
● at 30 °C recommended | 26.8 V |
● at 40 °C recommended | 26.6 V |
● at 50 °C recommended | 26.3 V |
Output | |
charging current maximum | 1.75 A |
output voltage at DC rated value | 24 V |
Safety | |
design of short-circuit protection | Battery fuse 20 A/32 V (solid-state circuitry blade-type fuse + support) |
design of the overload protection | Valve control |
Safety | |
operating resource protection class | Class III |
protection class | IP IP00 |
Approvals | |
certificate of suitability | |
● CE marking | Yes |
● UL approval | Yes |
● as approval for USA | cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 |
● cCSAus, Class 1, Division 2 | No |
● ATEX | No |
certificate of suitability | |
● EAC approval | Yes |
● shipbuilding approval | Yes |
shipbuilding approval | ABS, DNV GL |
Marine classification association | |
● American Bureau of Shipping Europe Ltd. (ABS) | Yes |
● DNV GL | Yes |
environmental conditions | |
Operating data note | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. |
ambient temperature | |
● during operation | -15 ... +50 °C |
● during transport -20 ... +50 °C | |
● during storage -20 ... +50 °C | |
relative temporary capacity loss at 20 °C in a month typical | 3% |
Service life | |
service life of energy storage | |
● typical | capacity falls to 80 % of original capacity (according to EUROBAT) |
● at 20 °C typical | 4 a |
● at 30 °C typical | 2 a |
● at 40 °C typical | 1 a |
● at 50 °C typical | 0.5 a |
ambient temperature during storage | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. |
Mechanics | |
type of electrical connection | spring-loaded terminals |
● for power supply unit | 1 screw terminal each for 0.08 ... 4 mm² for + BAT and - BAT |
product component included | Accessories pack with solid-state circuitry fuse 20 A and 30 A |
width of the enclosure | 186 mm |
height of the enclosure | 168 mm |
depth of the enclosure | 121 mm |
installation width | 206 mm |
mounting height | 188 mm |
fastening method | |
● wall mounting | Yes |
● standard rail mounting | NO |
● S7 rail mounting | No |
fastening method | can be screwed onto flat surface (keyhole mounting for hooking in to M4 screws) |
net weight | 6 kg |
number of cells | 12 |
battery capacity | 7 A·h |