Brand Name :SIEMENS
Model Number :6ES7331-7NF00-0AB0
Place of Origin :CHINA
MOQ :1PC
Price :EXW USD540-600
Payment Terms :T/T, Western Union,Paypal
Supply Ability :100PCS Every month
Delivery Time :8-15 work days
Packaging Details :carton
Accessory Type :Analogue Module
For Use With :S7-300 Series
Dimensions :13.10 x 15.10 x 5.10
Weight :0.4 Kg
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

SIEMENS 6ES7331-7NF00-0AB0 Analog Input Module for use with S7-300 Series

SIEMENS 6ES7331-7NF00-0AB0 Analog Input Module For Use With S7-300 Series

6ES73317NF000AB0 Siemens SIMATIC S7-300, Analog input SM 331, isolated, 8 AI; +/-5/10V, 1-5 V, +/-20 mA, 0/4 to 20 mA, 16 bit (55ms), Single rooting (50 V COM.), 1x 40-pole 6ES7331-7NF00-0AB0

Input current
from backplane bus 5 V DC, max.130 mA
Power loss
Power loss, typ.0.6 W
Analog inputs
Number of analog inputs8
permissible input voltage for voltage input (destructionlimit), max.50 V; Permanent
permissible input current for current input (destructionlimit), max.32 mA
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.16 bit; Unipolar: 15/15/15/15 bit; bipolar: 15 bit + sign/15 bit + sign/15 bit
+ sign/15 bit + sign
● Integration time, parameterizableYes; 10/ 16.67/ 20/ 100 ms
● Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10 Hz
Encoder
Connection of signal encoders
● for voltage measurementYes
● for current measurement as 2-wire transducerYes; with external transmitter; possible with separate supply for
transmitter
● for current measurement as 4-wire transducerYes
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-)0.1 %; At Ucm = 0 V or ±0.7 % at Ucm = 50 V
● Current, relative to input range, (+/-)0.3 %; At Ucm = 0 V or ±0.9 % at Ucm = 50 V
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)0.05%
● Current, relative to input range, (+/-)0.05%
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
● Diagnostic alarmYes; Parameterizable
● Limit value alarmYes; Parameterizable, channels 0 and 2
Diagnoses
● Diagnostic information readableYes
Diagnostics indication LED
● Group error SF (red)Yes
Isolation
Isolation tested with500 V DC
connection method / header
required front connector40-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.272 g